Data record gloss.temporary-protective-grounding.osha1910-269.order-of-connection
Verified 2026-11-02 Confidence: High
Under 29 CFR 1910.269, a protective ground goes on ground end first: the employee attaches the ground-end connection and then attaches the other end with a live-line tool, and a ground comes off in the reverse order, the grounding device taken off the line or equipment with a live-line tool before the ground-end connection is removed. For lines or equipment operating at or below the voltage given in the datum value the employer may permit insulating equipment other than a live-line tool, where the line or equipment is not energized at the time or the employer can demonstrate that each employee is protected from the hazards that would develop if it were. The duties are stated in paragraphs (n)(6)(i) and (n)(6)(ii).
Value: 600 V
| Step | Item | Detail |
|---|---|---|
| Source | 29 CFR 1910.269 | Regulation, clause (n)(6) |
| Data record | gloss.temporary-protective-grounding.osha1910-269.order-of-connection | Verified 2026-11-02 |
| Entry | Temporary protective grounding | No revisions |
- Subject
- Temporary protective grounding (Glossary)
- Kind
- Standard scope
- Source
- 29 CFR 1910.269, current edition, clause (n)(6), 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), OSHA. Regulation text. Agency copy of 29 CFR 1910.269
- Also stated in
- Source passage: 29 CFR 1910.269, paragraph (n)(6)(i), first sentence (eCFR current as of 2026-10-26).
Read the reference passage
(n)(6) Connecting and removing grounds
"The employer shall ensure that, when an employee attaches a ground to a line or to equipment, the employee attaches the ground-end connection first and then attaches the other end by means of a live-line tool."
29 CFR 1910.269, paragraph (n)(6)(i), first sentence, eCFR current as of 2026-10-26. Agency copy of 29 CFR 1910.269
The current standard governs; this passage is a public-domain description of the practice dated eCFR current as of 2026-10-26.
- Source passage: 29 CFR 1910.269, paragraph (n)(6)(ii), first sentence (eCFR current as of 2026-10-26).
Read the reference passage
(n)(6) Connecting and removing grounds
"The employer shall ensure that, when an employee removes a ground, the employee removes the grounding device from the line or equipment using a live-line tool before he or she removes the ground-end connection."
29 CFR 1910.269, paragraph (n)(6)(ii), first sentence, eCFR current as of 2026-10-26. Agency copy of 29 CFR 1910.269
The current standard governs; this passage is a public-domain description of the practice dated eCFR current as of 2026-10-26.
- FIST 5-1, section 6.7.1, page 23 (July 2005).
Read the reference passage
6.7.1 Ground-End Clamps
"Ground-end clamps of ground cable assemblies shall always be applied first. Clamp jaws and their point of attachment to a ground electrode (ground mat conductor, equipment ground bus, tower steel, etc.) should be wire brushed immediately before installation. The clamp must be tightened securely to provide a low resistance electrical bond and a secure mechanical connection."
FIST 5-1, section 6.7.1, page 23, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- FIST 5-1, section 6.7.2 A, page 24 (July 2005).
Read the reference passage
6.7.2 Circuit-End Clamps (arc flash hazard analysis required)
"Circuit-end or the working end clamps of ground cable assemblies shall be applied after the ground-end clamps are connected. The circuit or working end clamps shall always be connected and disconnected by means of hot sticks of adequate length to meet minimum approach distances given in Table 1 (Section 3), with the following exception: it is recognized that limiting dimensions in plant equipment often prohibit the use of hot sticks when attaching ground clamps to bus. [...] Remember, the bus is considered energized from a safety standpoint until properly grounded."
FIST 5-1, section 6.7.2 A, page 24, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- FIST 5-1, section 6.7.6, page 25 (July 2005).
Read the reference passage
6.7.6 Removal
"Protective grounds should be removed in reverse order from installation. The circuit-end clamps should be disconnected in succession, starting first with the farthest ground cable or circuit, in a manner that creates a safe exposure (minimum approach distance) to ungrounded circuit conductors as the grounds are removed. Ground-end clamps must be disconnected after the circuit-end clamps have been removed. Account for all protective grounds to ensure they have been removed before re-energizing the line or equipment."
FIST 5-1, section 6.7.6, page 25, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Source passage: 29 CFR 1910.269, paragraph (n)(6)(i), first sentence (eCFR current as of 2026-10-26).
- Beside
- gloss.temporary-protective-grounding.osha1910-269.placement; gloss.temporary-protective-grounding.osha1910-269.grounds-before-work; gloss.temporary-protective-grounding.nfpa70e.steps; gloss.temporary-protective-grounding.definition
History
| Date | Change |
|---|---|
| 2026-11-02 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record gloss.temporary-protective-grounding.osha1910-269.order-of-connection." Arc Flash Reference. 2026-11-02. https://www.arcflashreference.com/data/gloss.temporary-protective-grounding.osha1910-269.order-of-connection/.
Arc Flash Reference, Data record gloss.temporary-protective-grounding.osha1910-269.order-of-connection (Nov. 2, 2026), https://www.arcflashreference.com/data/gloss.temporary-protective-grounding.osha1910-269.order-of-connection/.
@misc{etr-data-gloss-temporary-protective-grounding-osha1910-269-order-of-connection,
title = {Data record gloss.temporary-protective-grounding.osha1910-269.order-of-connection},
howpublished = {\url{https://www.arcflashreference.com/data/gloss.temporary-protective-grounding.osha1910-269.order-of-connection/}},
organization = {Arc Flash Reference},
publisher = {Arc Flash Reference},
year = {2026},
note = {last substantive change 2026-11-02}
}{{cite web |title=Data record gloss.temporary-protective-grounding.osha1910-269.order-of-connection |website=Arc Flash Reference |publisher=Arc Flash Reference |url=https://www.arcflashreference.com/data/gloss.temporary-protective-grounding.osha1910-269.order-of-connection/ |date=2026-11-02 |access-date=}}