Steps eight and nine of clause 120.6 of NFPA 70E-2027 require temporary protective grounds before any part is touched where induced voltage or stored electrical energy is possible or where the de-energized parts could contact other exposed energized parts; the grounds are placed to protect each employee from shock, sized for the maximum fault current at the point of grounding over the clearing time, and of an impedance low enough to operate the protective devices, with ASTM F855 named in an informational note as an example standard for the equipment.

ProvenanceNFPA 70E-2027 supports data record gloss.temporary-protective-grounding.nfpa70e.steps, which is cited on the entry Temporary protective grounding.SOURCENFPA 70E-2027NFPA 70E-2027Licensed standard, clause 120.6(8)DATA RECORDgloss.temporary-protective-grounding.nfpa70e.stepsgloss.temporary-protecti..Verified 2026-10-27ENTRYTemporary protective groundingTemporary protective gro..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceNFPA 70E-2027Licensed standard, clause 120.6(8)
Data recordgloss.temporary-protective-grounding.nfpa70e.stepsVerified 2026-10-27
EntryTemporary protective groundingNo revisions
Subject
Temporary protective grounding (Glossary)
Kind
Standard scope
Source
NFPA 70E-2027, clause 120.6(8), Standard for Electrical Safety in the Workplace, NFPA. Publisher page