Arc flash boundary

Updated 2026-10-27

Data records

  • Article 100 of NFPA 70E-2027 defines the arc flash boundary, where an arc flash hazard exists, as the approach limit at which the incident energy equals the threshold value the definition states, the same value clause 130.5(E) uses for the incident energy analysis method. Source: NFPA 70E-2027, clause Article 100. Verified 2026-10-27. Record gloss.arc-flash-boundary.nfpa70e.definition
  • Clause 130.5(E) of NFPA 70E-2027 locates the arc flash boundary either by incident energy analysis or from the PPE category tables of clause 130.7(C)(15); clause 130.4(E) makes it independent of the shock protection boundaries, so it may be larger than the limited approach boundary, and clause 130.5(H) puts it on the equipment label. Source: NFPA 70E-2027, clause 130.5(E). Verified 2026-10-27. Record gloss.arc-flash-boundary.nfpa70e.determination