Data record gloss.arc-flash-boundary.nfpa70e.determination

Verified 2026-10-27 Confidence: High

Clause 130.5(E) of NFPA 70E-2027 locates the arc flash boundary either by incident energy analysis or from the PPE category tables of clause 130.7(C)(15); clause 130.4(E) makes it independent of the shock protection boundaries, so it may be larger than the limited approach boundary, and clause 130.5(H) puts it on the equipment label.

ProvenanceNFPA 70E-2027 supports data record gloss.arc-flash-boundary.nfpa70e.determination, which is cited on the entry Arc flash boundary.SOURCENFPA 70E-2027NFPA 70E-2027Licensed standard, clause 130.5(E)DATA RECORDgloss.arc-flash-boundary.nfpa70e.determinationgloss.arc-flash-boundary..Verified 2026-10-27ENTRYArc flash boundaryArc flash boundaryNo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceNFPA 70E-2027Licensed standard, clause 130.5(E)
Data recordgloss.arc-flash-boundary.nfpa70e.determinationVerified 2026-10-27
EntryArc flash boundaryNo revisions
Subject
Arc flash boundary (Glossary)
Kind
Standard scope
Source
NFPA 70E-2027, clause 130.5(E), Standard for Electrical Safety in the Workplace, NFPA. Publisher page

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-27created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record gloss.arc-flash-boundary.nfpa70e.determination." Arc Flash Reference. 2026-10-27. https://www.arcflashreference.com/data/gloss.arc-flash-boundary.nfpa70e.determination/.