Data record gloss.temporary-protective-grounding.osha1910-269.grounding-method

Verified 2026-10-28 Confidence: High

Appendix C to 29 CFR 1910.269 explains that a higher fault current generally brings a shorter clearing time for the same type of fault, so the grounding method maximizes the fault current through a low impedance connection to the lowest impedance ground available at the worksite, which is a grounded system neutral conductor where one is present. The explanation sits in section III.D.2.i of the appendix.

Provenance29 CFR 1910.269 supports data record gloss.temporary-protective-grounding.osha1910-269.grounding-method, which is cited on the entry Temporary protective grounding.SOURCE29 CFR 1910.26929 CFR 1910.269Regulation, clause Appendix C, III.D.2.iDATA RECORDgloss.temporary-protective-grounding.osha1910-269.grounding-methodgloss.temporary-protecti..Verified 2026-10-28ENTRYTemporary protective groundingTemporary protective gro..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
Source29 CFR 1910.269Regulation, clause Appendix C, III.D.2.i
Data recordgloss.temporary-protective-grounding.osha1910-269.grounding-methodVerified 2026-10-28
EntryTemporary protective groundingNo revisions
Subject
Temporary protective grounding (Glossary)
Kind
Standard scope
Source
29 CFR 1910.269, current edition, clause Appendix C, III.D.2.i, 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), OSHA. Regulation text. Agency copy of 29 CFR 1910.269
Also stated in
  • 29 CFR 1910.269, Appendix C, section III.D.2.i (eCFR current as of 2026-10-26).
    Read the reference passage
    "Generally, the higher the fault current, the shorter the clearing times for the same type of fault. Therefore, to ensure the fastest available clearing time, the grounding method must maximize the fault current with a low impedance connection to ground. The employer accomplishes this objective by grounding the circuit conductors to the best ground available at the worksite. Thus, the employer must ground to a grounded system neutral conductor, if one is present."

    29 CFR 1910.269, Appendix C, section III.D.2.i, eCFR current as of 2026-10-26. Agency copy of 29 CFR 1910.269

    The current standard governs; this passage is a public-domain description of the practice dated eCFR current as of 2026-10-26.

Beside
gloss.temporary-protective-grounding.nfpa70e.steps

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-28created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record gloss.temporary-protective-grounding.osha1910-269.grounding-method." Arc Flash Reference. 2026-10-28. https://www.arcflashreference.com/data/gloss.temporary-protective-grounding.osha1910-269.grounding-method/.