Appendix C to 29 CFR 1910.269 explains that a higher fault current generally brings a shorter clearing time for the same type of fault, so the grounding method maximizes the fault current through a low impedance connection to the lowest impedance ground available at the worksite, which is a grounded system neutral conductor where one is present. The explanation sits in section III.D.2.i of the appendix.
| Step | Item | Detail |
|---|---|---|
| Source | 29 CFR 1910.269 | Regulation, clause Appendix C, III.D.2.i |
| Data record | gloss.temporary-protective-grounding.osha1910-269.grounding-method | Verified 2026-10-28 |
| Entry | Temporary protective grounding | No revisions |
- Subject
- Temporary protective grounding (Glossary)
- Kind
- Standard scope
- Source
- 29 CFR 1910.269, current edition, clause Appendix C, III.D.2.i, 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), OSHA. Regulation text. Agency copy of 29 CFR 1910.269
- Also stated in
- 29 CFR 1910.269, Appendix C, section III.D.2.i (eCFR current as of 2026-10-26).
Read the reference passage
"Generally, the higher the fault current, the shorter the clearing times for the same type of fault. Therefore, to ensure the fastest available clearing time, the grounding method must maximize the fault current with a low impedance connection to ground. The employer accomplishes this objective by grounding the circuit conductors to the best ground available at the worksite. Thus, the employer must ground to a grounded system neutral conductor, if one is present."
29 CFR 1910.269, Appendix C, section III.D.2.i, eCFR current as of 2026-10-26. Agency copy of 29 CFR 1910.269
The current standard governs; this passage is a public-domain description of the practice dated eCFR current as of 2026-10-26.
- 29 CFR 1910.269, Appendix C, section III.D.2.i (eCFR current as of 2026-10-26).
- Beside
- gloss.temporary-protective-grounding.nfpa70e.steps
History
| Date | Change |
|---|---|
| 2026-10-28 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record gloss.temporary-protective-grounding.osha1910-269.grounding-method." Arc Flash Reference. 2026-10-28. https://www.arcflashreference.com/data/gloss.temporary-protective-grounding.osha1910-269.grounding-method/.
Arc Flash Reference, Data record gloss.temporary-protective-grounding.osha1910-269.grounding-method (Oct. 28, 2026), https://www.arcflashreference.com/data/gloss.temporary-protective-grounding.osha1910-269.grounding-method/.
@misc{etr-data-gloss-temporary-protective-grounding-osha1910-269-grounding-method,
title = {Data record gloss.temporary-protective-grounding.osha1910-269.grounding-method},
howpublished = {\url{https://www.arcflashreference.com/data/gloss.temporary-protective-grounding.osha1910-269.grounding-method/}},
organization = {Arc Flash Reference},
publisher = {Arc Flash Reference},
year = {2026},
note = {last substantive change 2026-10-28}
}{{cite web |title=Data record gloss.temporary-protective-grounding.osha1910-269.grounding-method |website=Arc Flash Reference |publisher=Arc Flash Reference |url=https://www.arcflashreference.com/data/gloss.temporary-protective-grounding.osha1910-269.grounding-method/ |date=2026-10-28 |access-date=}}