Data record gloss.normal-operating-condition.nfpa70e.definition

Verified 2026-10-27 Confidence: High

The first exception to clause 110.2(B) of NFPA 70E-2027 allows normal operation of equipment without an electrically safe work condition only when the equipment is in a normal operating condition, which requires all seven of the following: properly installed, properly maintained, rated for the available fault current, used in accordance with its listing, labeling and manufacturer's instructions, doors closed and secured, all covers in place and secured, and no evidence of impending failure.

ProvenanceNFPA 70E-2027 supports data record gloss.normal-operating-condition.nfpa70e.definition, which is cited on the entry Normal operating condition.SOURCENFPA 70E-2027NFPA 70E-2027Licensed standard, clause 110.2(B) Exception No. 1DATA RECORDgloss.normal-operating-condition.nfpa70e.definitiongloss.normal-operating-c..Verified 2026-10-27ENTRYNormal operating conditionNormal operating conditionNo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceNFPA 70E-2027Licensed standard, clause 110.2(B) Exception No. 1
Data recordgloss.normal-operating-condition.nfpa70e.definitionVerified 2026-10-27
EntryNormal operating conditionNo revisions
Subject
Normal operating condition (Glossary)
Kind
Definition
Source
NFPA 70E-2027, clause 110.2(B) Exception No. 1, Standard for Electrical Safety in the Workplace, NFPA. Publisher page

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-27created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record gloss.normal-operating-condition.nfpa70e.definition." Arc Flash Reference. 2026-10-27. https://www.arcflashreference.com/data/gloss.normal-operating-condition.nfpa70e.definition/.