Normal operating condition

Updated 2026-10-27

Data records

  • The first exception to clause 110.2(B) of NFPA 70E-2027 allows normal operation of equipment without an electrically safe work condition only when the equipment is in a normal operating condition, which requires all seven of the following: properly installed, properly maintained, rated for the available fault current, used in accordance with its listing, labeling and manufacturer's instructions, doors closed and secured, all covers in place and secured, and no evidence of impending failure. Source: NFPA 70E-2027, clause 110.2(B) Exception No. 1. Verified 2026-10-27. Record gloss.normal-operating-condition.nfpa70e.definition
  • Table 130.5(C)(3) of NFPA 70E-2027 distinguishes operation of a circuit breaker, switch, contactor or starter in a normal operating condition from operation in an abnormal condition when it estimates the likelihood of an arc flash occurrence. Source: NFPA 70E-2027, clause Table 130.5(C)(3). Verified 2026-10-27. Record gloss.normal-operating-condition.nfpa70e.likelihood