Data record gloss.live-line-tool.osha1910-269.design-withstand
Verified 2026-11-02 Confidence: High
Under 29 CFR 1910.269, live-line tool rods, tubes and poles are designed and built to withstand a minimum test stated per unit of length, given in the datum value for fiberglass-reinforced plastic and for wood, or other tests the employer can demonstrate are equivalent; the regulation's note deems rod and tube that meet ASTM F711 to comply. The requirement is paragraph (j)(1).
Value: fiberglass-reinforced plastic: 100,000 volts per foot (328,100 volts per meter) of length for 5 minutes; wood: 75,000 volts per foot (246,100 volts per meter) of length for 3 minutes
| Step | Item | Detail |
|---|---|---|
| Source | 29 CFR 1910.269 | Regulation, clause (j)(1) |
| Data record | gloss.live-line-tool.osha1910-269.design-withstand | Verified 2026-11-02 |
| Entry | Live line tool | No revisions |
- Subject
- Live line tool (Glossary)
- Kind
- Standard scope
- Source
- 29 CFR 1910.269, current edition, clause (j)(1), 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), OSHA. Regulation text. Agency copy of 29 CFR 1910.269
- Also stated in
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 15-17.a, PDF page 170, printed 15-6, the lead sentences of section 15-17 name the ASTM F18 series and are not excerpted (29 November 1996).
Read the reference passage
15-17.a. Fiberglass
"A fiberglass tool must have withstood 100,000 volts ac per foot (300 millimeters) of length for 5 minutes."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 15-17.a, PDF page 170, printed 15-6, the lead sentences of section 15-17 name the ASTM F18 series and are not excerpted, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 15-17.a, PDF page 170, printed 15-6, the lead sentences of section 15-17 name the ASTM F18 series and are not excerpted (29 November 1996).
- Beside
- gloss.live-line-tool.osha1910-269.condition-and-testing; gloss.rubber-insulating-equipment.osha1910-137.in-service-care; gloss.temporary-protective-grounding.osha1910-269.order-of-connection; gloss.restricted-approach-boundary.osha1910-269.minimum-approach-distance
History
| Date | Change |
|---|---|
| 2026-11-02 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record gloss.live-line-tool.osha1910-269.design-withstand." Arc Flash Reference. 2026-11-02. https://www.arcflashreference.com/data/gloss.live-line-tool.osha1910-269.design-withstand/.
Arc Flash Reference, Data record gloss.live-line-tool.osha1910-269.design-withstand (Nov. 2, 2026), https://www.arcflashreference.com/data/gloss.live-line-tool.osha1910-269.design-withstand/.
@misc{etr-data-gloss-live-line-tool-osha1910-269-design-withstand,
title = {Data record gloss.live-line-tool.osha1910-269.design-withstand},
howpublished = {\url{https://www.arcflashreference.com/data/gloss.live-line-tool.osha1910-269.design-withstand/}},
organization = {Arc Flash Reference},
publisher = {Arc Flash Reference},
year = {2026},
note = {last substantive change 2026-11-02}
}{{cite web |title=Data record gloss.live-line-tool.osha1910-269.design-withstand |website=Arc Flash Reference |publisher=Arc Flash Reference |url=https://www.arcflashreference.com/data/gloss.live-line-tool.osha1910-269.design-withstand/ |date=2026-11-02 |access-date=}}