Data record std.nfpa-70e.structure.130-5-g-analysis-method
Verified 2026-10-27 Confidence: High
Clause 130.5(G) of NFPA 70E-2027 bases the incident energy analysis on the working distance for the task, requires it to account for the characteristics of the overcurrent protective device and its clearing time including the condition of maintenance, requires an update when a system change could affect the result, and sets a maximum interval for its review; Table 130.5(G) then selects the protective equipment by incident energy band, with arc-rated clothing rated at or above the estimated energy in every band.
| Step | Item | Detail |
|---|---|---|
| Source | NFPA 70E-2027 | Licensed standard, clause 130.5(G) |
| Data record | std.nfpa-70e.structure.130-5-g-analysis-method | Verified 2026-10-27 |
| Entry | Standard for Electrical Safety in the Workplace | No revisions |
- Subject
- Standard for Electrical Safety in the Workplace (Standards)
- Kind
- Standard scope
- Source
- NFPA 70E-2027, clause 130.5(G), Standard for Electrical Safety in the Workplace, NFPA. Publisher page
History
| Date | Change |
|---|---|
| 2026-10-27 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record std.nfpa-70e.structure.130-5-g-analysis-method." Arc Flash Reference. 2026-10-27. https://www.arcflashreference.com/data/std.nfpa-70e.structure.130-5-g-analysis-method/.
Arc Flash Reference, Data record std.nfpa-70e.structure.130-5-g-analysis-method (Oct. 27, 2026), https://www.arcflashreference.com/data/std.nfpa-70e.structure.130-5-g-analysis-method/.
@misc{etr-data-std-nfpa-70e-structure-130-5-g-analysis-method,
title = {Data record std.nfpa-70e.structure.130-5-g-analysis-method},
howpublished = {\url{https://www.arcflashreference.com/data/std.nfpa-70e.structure.130-5-g-analysis-method/}},
organization = {Arc Flash Reference},
publisher = {Arc Flash Reference},
year = {2026},
note = {last substantive change 2026-10-27}