Data record std.nfpa-70e.structure.130-3-c-exemptions

Verified 2026-10-27 Confidence: High

Clause 130.3(C) of NFPA 70E-2027 exempts four kinds of work by a qualified person using the Chapter 1 practices and protective equipment from the permit: testing, troubleshooting and voltage measuring; thermography, ultrasound and visual inspection that do not cross the restricted approach boundary; access to and egress from an area with energized equipment where no electrical work is done and the restricted approach boundary is not crossed; and general housekeeping and non-electrical tasks with the restricted approach boundary not crossed.

ProvenanceNFPA 70E-2027 supports data record std.nfpa-70e.structure.130-3-c-exemptions, which is cited on the entry Standard for Electrical Safety in the Workplace.SOURCENFPA 70E-2027NFPA 70E-2027Licensed standard, clause 130.3(C)DATA RECORDstd.nfpa-70e.structure.130-3-c-exemptionsstd.nfpa-70e.structure.1..Verified 2026-10-27ENTRYStandard for Electrical Safety in the WorkplaceStandard for Electrical ..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceNFPA 70E-2027Licensed standard, clause 130.3(C)
Data recordstd.nfpa-70e.structure.130-3-c-exemptionsVerified 2026-10-27
EntryStandard for Electrical Safety in the WorkplaceNo revisions
Subject
Standard for Electrical Safety in the Workplace (Standards)
Kind
Standard scope
Source
NFPA 70E-2027, clause 130.3(C), Standard for Electrical Safety in the Workplace, NFPA. Publisher page

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-27created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record std.nfpa-70e.structure.130-3-c-exemptions." Arc Flash Reference. 2026-10-27. https://www.arcflashreference.com/data/std.nfpa-70e.structure.130-3-c-exemptions/.