Data record std.nfpa-70e.structure.120-5-b-6-testing
Verified 2026-10-27 Confidence: High
Clause 120.5(B)(6) of NFPA 70E-2027 requires the procedure to establish the test instrument, the protective equipment, the person who verifies the instrument on a known voltage source before and after use, and the boundary of the electrically safe work condition; every exposed conductor or part inside that boundary is tested before it is touched, retested when circuit conditions change or the job location has been left unattended, and additional test methods are used where the absence-of-voltage test alone does not confirm de-energization.
| Step | Item | Detail |
|---|---|---|
| Source | NFPA 70E-2027 | Licensed standard, clause 120.5(B)(6) |
| Data record | std.nfpa-70e.structure.120-5-b-6-testing | Verified 2026-10-27 |
| Entry | Standard for Electrical Safety in the Workplace | No revisions |
- Subject
- Standard for Electrical Safety in the Workplace (Standards)
- Kind
- Standard scope
- Source
- NFPA 70E-2027, clause 120.5(B)(6), Standard for Electrical Safety in the Workplace, NFPA. Publisher page
History
| Date | Change |
|---|---|
| 2026-10-27 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record std.nfpa-70e.structure.120-5-b-6-testing." Arc Flash Reference. 2026-10-27. https://www.arcflashreference.com/data/std.nfpa-70e.structure.120-5-b-6-testing/.
Arc Flash Reference, Data record std.nfpa-70e.structure.120-5-b-6-testing (Oct. 27, 2026), https://www.arcflashreference.com/data/std.nfpa-70e.structure.120-5-b-6-testing/.
@misc{etr-data-std-nfpa-70e-structure-120-5-b-6-testing,
title = {Data record std.nfpa-70e.structure.120-5-b-6-testing},
howpublished = {\url{https://www.arcflashreference.com/data/std.nfpa-70e.structure.120-5-b-6-testing/}},
organization = {Arc Flash Reference},
publisher = {Arc Flash Reference},
year = {2026},
note = {last substantive change 2026-10-27}
}{{cite web |title=Data record std.nfpa-70e.structure.120-5-b-6-testing |website=Arc Flash Reference |publisher=Arc Flash Reference |url=https://www.arcflashreference.com/data/std.nfpa-70e.structure.120-5-b-6-testing/ |date=2026-10-27 |access-date=}}