Arc Energy Reduction Performance

Updated 2026-10-24

RelationshipsArc Energy Reduction Performance is governed by IEEE 1584-2018 and applies to no listed equipment.IEEE Guide for Performing Arc-Flash Hazard CalculationsIEEE 1584-2018Arc Energy Reduction PerformanceArc Energy Reduction Performance
Relationships. Governing standards on the left, equipment classes the test applies to on the right, as recorded for this entry.
Relationships: relationships recorded for this entry.
RelationshipEntry
Governing standardIEEE 1584-2018 (IEEE Guide for Performing Arc-Flash Hazard Calculations)

Data records

  • Arc Energy Reduction Performance is specified for microprocessor-based protective relays in acceptance testing at clause 7.9.2.B.6 of ANSI/NETA ATS-2025. Value: microprocessor-based protective relays. Source: ANSI/NETA ATS-2025, clause 7.9.2.B.6. Verified 2026-10-13. Record tests.arc-energy-reduction-performance.equipment.relay.acceptance
  • Arc Energy Reduction Performance is addressed in ANSI/NETA ATS-2025. Source: ANSI/NETA ATS-2025, clause 7.9.2.B.6. Verified 2026-10-13. Record tests.arc-energy-reduction-performance.governed-by.ansi-neta-ats
  • Clause 6.8 of IEEE 1584-2018 computes the total arcing current at a location from the total bolted fault current and assigns each upstream protective device its proportional share of that arcing current, which is the current at which that device's clearing time is read from its time-current curve. Source: IEEE 1584-2018, clause 6.8. Verified 2026-10-24. Record tests.arc-energy-reduction-performance.ieee1584.arcing-current
  • In IEEE 1584-2018 the clearing time of the protective device stands in for the arc duration, apart from the cases clause 6.9.1 describes, and clause 6.9.1 has the device's time-current curve read at both the arcing current and the reduced arcing current of clause 4.5, with the longer clearing time governing the incident energy. Source: IEEE 1584-2018, clause 3.1, 6.9.1. Verified 2026-10-24. Record tests.arc-energy-reduction-performance.ieee1584.clearing-time
  • IEEE 1584-2018 prescribes no field test of arc energy reduction or of any protective device; its field content is the data collection of clause 6.2, which calls for the installed fuse types and ratings, trip unit settings and relay settings to be checked in the field against what the study assumed. Source: IEEE 1584-2018, clause 6.2. Verified 2026-10-24. Record tests.arc-energy-reduction-performance.ieee1584.no-field-test
  • An arc-flash study performed with IEEE 1584-2018 reports, for each location, the incident energy at the working distance and the arc-flash boundary, which clause 3.1 defines as the distance from the arc source at which the calculated incident energy falls to the threshold value stated in the definition. Source: IEEE 1584-2018, clause 3.1, 6.11. Verified 2026-10-24. Record tests.arc-energy-reduction-performance.ieee1584.study-outputs
  • The test method is named Arc Energy Reduction Performance. Value: Arc Energy Reduction Performance. Source: Electrical Testing Reference editorial taxonomy, 2026-10 edition. Verified 2026-10-13. Record tests.arc-energy-reduction-performance.title

Sources

  • ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.9.2.B.6. Held as: Purchased single-user copy. Publisher page
  • Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
  • IEEE 1584-2018, Guide for Performing Arc-Flash Hazard Calculations, 2018 edition, IEEE. Cited: clause 6.8; clause 3.1, 6.9.1; clause 6.2; clause 3.1, 6.11. Held as: Purchased single-user copy.

Obtaining the documents

Changelog (14 entries)
DateRevisionChange
2026-10-24created (tests.arc-energy-reduction-performance.ieee1584.arcing-current)
2026-10-24review_status unreviewed -> software_reviewed (tests.arc-energy-reduction-performance.ieee1584.arcing-current)
2026-10-24created (tests.arc-energy-reduction-performance.ieee1584.clearing-time)
2026-10-24revised (tests.arc-energy-reduction-performance.ieee1584.clearing-time)
2026-10-24review_status unreviewed -> software_reviewed (tests.arc-energy-reduction-performance.ieee1584.clearing-time)
2026-10-24created (tests.arc-energy-reduction-performance.ieee1584.no-field-test)
2026-10-24revised (tests.arc-energy-reduction-performance.ieee1584.no-field-test)
2026-10-24review_status unreviewed -> software_reviewed (tests.arc-energy-reduction-performance.ieee1584.no-field-test)
2026-10-24created (tests.arc-energy-reduction-performance.ieee1584.study-outputs)
2026-10-24revised (tests.arc-energy-reduction-performance.ieee1584.study-outputs)
2026-10-24review_status unreviewed -> software_reviewed (tests.arc-energy-reduction-performance.ieee1584.study-outputs)
2026-10-13created (tests.arc-energy-reduction-performance.equipment.relay.acceptance)
2026-10-13created (tests.arc-energy-reduction-performance.governed-by.ansi-neta-ats)
2026-10-13created (tests.arc-energy-reduction-performance.title)

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Arc Energy Reduction Performance." Arc Flash Reference. 2026-10-24. https://www.arcflashreference.com/tests/arc-energy-reduction-performance/.